Grounding Transformers – Electrical Design, Transformer Design, and Distribution Transformer Design

Grounding is clearly one of the most important aspects of electrical design, but it steadfastly continues to be misinterpreted and misunderstood. Millions of dollars in liability and loss can be attributed to ground-fault arcing; thus, grounding-related issues should top the checklists of any electrical contractor.

Grounding Transformers:

Simply put, a grounding transformer is used to provide a ground path to either an ungrounded “Y” or a delta connected system. Grounding transformers are typically used to:

 

  1. Provide a relatively low impedance path to ground, thereby maintaining the system neutral at or near ground potential
  2. Limit the magnitude of transient over voltages when re-striking ground faults occur
  3. Provide a source of ground fault current during line-to-ground faults
  4. Permit the connection of phase to neutral loads when desired

 

If a single line-to-ground fault occurs on an ungrounded or isolated system, ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
ThanaBhatti
no return path exists for the fault current, thus no current flows. The system will continue to operate but the other two un-faulted lines will rise in voltage by the square root of 3, resulting in overstressing of the transformer insulation and other associated components on the system by 173%. MOV lightning arresters are particularly susceptible to damage from heating by leakage across the blocks even if the voltage increase is not sufficient to flash over. A grounding transformer provides a ground path to prevent this.

Large multi-turbine wind farms provide an example of the use of grounding transformers for fault protection on ungrounded lines. In many wind farms the substation transformer provides the sole ground source for the distribution system. When a ground fault on a collector cable causes the substation circuit breaker for that cable to open, the wind turbine string becomes isolated from the ground source.

The turbines do not always detect this fault or the fact that the string is isolated and ungrounded; thus the generators continue to energize the collector cable, and the voltages between the un-faulted cables and the ground rise far above the normal voltage magnitude as described above. A grounding transformer placed on the turbine string provides a ground path in the event the string becomes isolated from the system ground.

Construction:

Grounding transformers are normally constructed either with

 

  1. A ZigZag (Zn) connected winding with or without an auxiliary winding or
  2. As a Wye (Ynd) connected winding with a delta connected secondary that may or may not be used to supply auxiliary power

 

The geometry of the Zig-Zag connection is useful to limit circulation of third harmonics and can be used without a Delta connected winding or the 4- or 5-leg core design normally used for this purpose in distribution and power transformers. Eliminating the need for a secondary winding can make this option both less expensive and smaller than a comparable two-winding grounding transformer. Furthermore, use of a Zig-Zag transformer provides grounding with a smaller unit than a two-winding Wye-Delta transformer providing the same zero sequence impedance.

Wye connected grounding transformers, on the other hand, require either a delta connected secondary or the application of 4 or 5 leg core construction to provide a return flux path for unbalanced loading associated with this primary connection. Since it is often desirable to provide auxiliary power from the grounding transformer secondary winding, this benefit can sway the end user to specify a two-winding grounding transformer in lieu of a Zig-Zag connection. The current trend in wind farm designs is toward the Wye connected primary with a delta secondary.

It is important to understand that both Zig-Zag and two-winding grounding transformers can be provided with the ability to provide auxiliary power, and this can be either a Wye or Delta connected load.

A solidly grounded system using a grounding transformer offers many safety improvements over an ungrounded system. However, the ground transformer alone lacks the current limiting ability of a resistive grounding system. For this reason, neutral ground resistors are often used in conjunction with the grounding transformer to limit neutral ground fault current magnitude. Their ohm values should be specified to allow high enough ground fault current flow to permit reliable operation of the protective relaying equipment, but low enough to limit thermal damage.

How to Specify a Grounding Transformer

The basic parameters required for quoting a grounding transformer are:

 

 

Related Posts

Leave a Reply

Your email address will not be published. Required fields are marked *